● Zones: tank/line/metering pump/final filter–spinneret as independent control zones.
● Sensors: high-accuracy PT100 in each zone with 2oo3 or main/standby redundancy. Place measurement points on pipe outer wall, in the fluid (where possible), and at jacket medium outlet.
● Control algorithms:
● Cascade PID: master loop on dope temperature setpoint; secondary loop on jacket heat-medium temperature for fast disturbance rejection.
● Feedforward: include ambient temperature and flow changes as feedforward to pre-adjust control valves and suppress gradients.
● Gradient target: zone temperature deviation < ±0.5°C. Optimize insulation, minimize bare flanges, and use equal-length manifolds for balanced branch flows.
● Actuators:
● High-precision control valves or VFD-driven thermal fluid pumps for jacket oil/water flow and temperature. For spinneret proximity, use compact mold-temperature controllers with PID for point control.